TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 80 A - 24 V AC 50/60 Hz coil LC1D80B7

TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 80 A - 24 V AC 50/60 Hz coil LC1D80B7

SKU: LC1D80B7 Category: Tag:

Compare

Description

Main

range

TeSys

product name

TeSys D

product or component type

Contactor

device short name

LC1D

contactor application

Motor control
Resistive load

utilisation category

AC-4
AC-1
AC-3

poles description

3P

power pole contact composition

3 NO

[Ue] rated operational voltage

Power circuit: <= 300 V DC 25…400 Hz
Power circuit: <= 690 V AC

[Ie] rated operational current

125 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit

motor power kW

22 kW at 220…230 V AC 50/60 Hz (AC-3)
37 kW at 380…400 V AC 50/60 Hz (AC-3)
45 kW at 415…440 V AC 50/60 Hz (AC-3)
55 kW at 500 V AC 50/60 Hz (AC-3)
45 kW at 660…690 V AC 50/60 Hz (AC-3)
45 kW at 1000 V AC 50/60 Hz (AC-3)
15 kW at 400 V AC 50/60 Hz (AC-4)

motor power HP (UL / CSA)

20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
7.5 hp at 115 V AC 50/60 Hz for 1 phase motors
15 hp at 230/240 V AC 50/60 Hz for 1 phase motors
25 hp at 230/240 V AC 50/60 Hz for 3 phases motors
60 hp at 460/480 V AC 50/60 Hz for 3 phases motors
60 hp at 575/600 V AC 50/60 Hz for 3 phases motors

control circuit type

AC at 50/60 Hz

[Uc] control circuit voltage

24 V AC 50/60 Hz

auxiliary contact composition

1 NO + 1 NC

[Uimp] rated impulse withstand voltage

8 kV conforming to IEC 60947

overvoltage category

III

[Ith] conventional free air thermal current

10 A (at 60 °C) for signalling circuit
125 A (at 60 °C) for power circuit

Irms rated making capacity

140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1100 A at 440 V for power circuit conforming to IEC 60947

rated breaking capacity

1100 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current

640 A 40 °C – 10 s for power circuit
990 A 40 °C – 1 s for power circuit
135 A 40 °C – 10 min for power circuit
320 A 40 °C – 1 min for power circuit
100 A – 1 s for signalling circuit
120 A – 500 ms for signalling circuit
140 A – 100 ms for signalling circuit

associated fuse rating

10 A gG for signalling circuit conforming to IEC 60947-5-1
200 A gG at <= 690 V coordination type 1 for power circuit
160 A gG at <= 690 V coordination type 2 for power circuit

average impedance

0.8 mOhm – Ith 125 A 50 Hz for power circuit

[Ui] rated insulation voltage

Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Power circuit: 1000 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified

electrical durability

0.8 Mcycles 125 A AC-1 at Ue <= 440 V
1.5 Mcycles 80 A AC-3 at Ue <= 440 V

power dissipation per pole

5.1 W AC-3
12.5 W AC-1

safety cover

With

mounting support

Plate
Rail

standards

CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508

product certifications

UL
GOST
DNV
BV
CSA
RINA
LROS (Lloyds register of shipping)
GL
CCC

connections – terminals

Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: connector 1 cable(s) 4…50 mm²flexible without cable end
Power circuit: connector 2 cable(s) 4…25 mm²flexible without cable end
Power circuit: connector 1 cable(s) 4…50 mm²flexible with cable end
Power circuit: connector 2 cable(s) 4…16 mm²flexible with cable end
Power circuit: connector 1 cable(s) 4…50 mm²solid without cable end
Power circuit: connector 2 cable(s) 4…25 mm²solid without cable end

tightening torque

Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver Philips No 2
Power circuit: 9 N.m – on connector – with screwdriver flat Ø 6 to Ø 8 mm
Power circuit: 9 N.m – on connector hexagonal screw head 4 mm

operating time

20…35 ms closing
6…20 ms opening

safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

mechanical durability

4 Mcycles

maximum operating rate

3600 cyc/h 60 °C

Complementary

coil technology

Without built-in suppressor module

control circuit voltage limits

Operational: 0.85…1.1 Uc AC 60 Hz (at 55 °C)
Drop-out: 0.3…0.6 Uc AC 50/60 Hz (at 55 °C)
Operational: 0.8…1.1 Uc AC 50 Hz (at 55 °C)

inrush power in VA

245 VA 60 Hz cos phi 0.75 (at 20 °C)
245 VA 50 Hz cos phi 0.75 (at 20 °C)

hold-in power consumption in VA

26 VA 60 Hz cos phi 0.3 (at 20 °C)
26 VA 50 Hz cos phi 0.3 (at 20 °C)

heat dissipation

6…10 W at 50/60 Hz

auxiliary contacts type

type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1

signalling circuit frequency

25…400 Hz

minimum switching current

5 mA for signalling circuit

minimum switching voltage

17 V for signalling circuit

non-overlap time

1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact

insulation resistance

> 10 MOhm for signalling circuit

Environment

IP degree of protection

IP20 front face conforming to IEC 60529

protective treatment

TH conforming to IEC 60068-2-30

pollution degree

3

ambient air temperature for operation

-5…60 °C

ambient air temperature for storage

-60…80 °C

permissible ambient air temperature around the device

-40…70 °C at Uc

operating altitude

3000 m without

fire resistance

850 °C conforming to IEC 60695-2-1

flame retardance

V1 conforming to UL 94

mechanical robustness

Vibrations contactor open: 2 Gn, 5…300 Hz
Shocks contactor open: 8 Gn for 11 ms
Vibrations contactor closed: 3 Gn, 5…300 Hz
Shocks contactor closed: 10 Gn for 11 ms

height

127 mm

width

85 mm

depth

130 mm

net weight

1.59 kg

Offer Sustainability

Sustainable offer status

Green Premium product

REACh Regulation

REACh Declaration

EU RoHS Directive

Compliant
EU RoHS Declaration

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

China RoHS declaration

Environmental Disclosure

Product Environmental Profile

Circularity Profile

No need of specific recycling operations

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Contractual warranty

Warranty

18 months

Reviews

There are no reviews yet.

Be the first to review “TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 80 A - 24 V AC 50/60 Hz coil LC1D80B7”

Your email address will not be published. Required fields are marked *