range | TeSys | |
---|
product name | TeSys D | |
---|
product or component type | Contactor | |
---|
device short name | LC1D | |
---|
contactor application | Resistive load
Motor control | |
---|
utilisation category | AC-1
AC-4
AC-3 | |
---|
poles description | 3P | |
---|
power pole contact composition | 3 NO | |
---|
[Ue] rated operational voltage | Power circuit: <= 300 V DC 25…400 Hz
Power circuit: <= 1000 V AC | |
---|
[Ie] rated operational current | 125 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
95 A (at <60 °C) at <= 440 V AC AC-3 for power circuit | |
---|
motor power kW | 45 kW at 415…440 V AC 50/60 Hz (AC-3)
55 kW at 500 V AC 50/60 Hz (AC-3)
45 kW at 660…690 V AC 50/60 Hz (AC-3)
45 kW at 1000 V AC 50/60 Hz (AC-3)
15 kW at 400 V AC 50/60 Hz (AC-4)
25 kW at 220…230 V AC 50/60 Hz (AC-3)
45 kW at 380…400 V AC 50/60 Hz (AC-3) | |
---|
motor power HP (UL / CSA) | 20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
7.5 hp at 115 V AC 50/60 Hz for 1 phase motors
15 hp at 230/240 V AC 50/60 Hz for 1 phase motors
25 hp at 230/240 V AC 50/60 Hz for 3 phases motors
60 hp at 460/480 V AC 50/60 Hz for 3 phases motors
60 hp at 575/600 V AC 50/60 Hz for 3 phases motors | |
---|
control circuit type | DC standard | |
---|
[Uc] control circuit voltage | 110 V DC | |
---|
auxiliary contact composition | 1 NO + 1 NC | |
---|
[Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 | |
---|
overvoltage category | III | |
---|
[Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit
125 A (at 60 °C) for power circuit | |
---|
Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1100 A at 440 V for power circuit conforming to IEC 60947 | |
---|
rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 | |
---|
[Icw] rated short-time withstand current | 1100 A 40 °C – 1 s for power circuit
135 A 40 °C – 10 min for power circuit
800 A 40 °C – 10 s for power circuit
400 A 40 °C – 1 min for power circuit
100 A – 1 s for signalling circuit
120 A – 500 ms for signalling circuit
140 A – 100 ms for signalling circuit | |
---|
associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1
200 A gG at <= 690 V coordination type 1 for power circuit
160 A gG at <= 690 V coordination type 2 for power circuit | |
---|
average impedance | 0.8 mOhm – Ith 125 A 50 Hz for power circuit | |
---|
[Ui] rated insulation voltage | Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Power circuit: 1000 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified | |
---|
electrical durability | 1.2 Mcycles 95 A AC-3 at Ue <= 440 V
1.3 Mcycles 125 A AC-1 at Ue <= 440 V | |
---|
power dissipation per pole | 12.5 W AC-1
7.2 W AC-3 | |
---|
safety cover | With | |
---|
mounting support | Rail
Plate | |
---|
standards | CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508 | |
---|
product certifications | GOST
CCC
RINA
DNV
LROS (Lloyds register of shipping)
BV
GL | |
---|
connections – terminals | Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: connector 1 cable(s) 4…50 mm²flexible without cable end
Power circuit: connector 2 cable(s) 4…25 mm²flexible without cable end
Power circuit: connector 1 cable(s) 4…50 mm²flexible with cable end
Power circuit: connector 2 cable(s) 4…16 mm²flexible with cable end
Power circuit: connector 1 cable(s) 4…50 mm²solid without cable end
Power circuit: connector 2 cable(s) 4…25 mm²solid without cable end | |
---|
tightening torque | Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver Philips No 2
Power circuit: 9 N.m – on connector – with screwdriver flat Ø 6 to Ø 8 mm
Power circuit: 9 N.m – on connector hexagonal screw head 4 mm | |
---|
operating time | 95…130 ms closing
20…35 ms opening | |
---|
safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 | |
---|
mechanical durability | 4 Mcycles | |
---|
maximum operating rate | 3600 cyc/h 60 °C | |
---|