range
|
TeSys
|
|
product name
|
TeSys D
|
|
product or component type
|
Contactor
|
|
device short name
|
LC1D
|
|
contactor application
|
Resistive load
Motor control
|
|
utilisation category
|
AC-1
AC-4
AC-3
|
|
poles description
|
3P
|
|
power pole contact composition
|
3 NO
|
|
[Ue] rated operational voltage
|
Power circuit <= 690 V AC 25…400 Hz
Power circuit <= 300 V DC
|
|
[Ie] rated operational current
|
18 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit
32 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
|
|
motor power kW
|
4Â kW 220…230 V AC 50/60 Hz AC-3)
7.5Â kW 380…400 V AC 50/60 Hz AC-3)
9Â kW 415…440 V AC 50/60 Hz AC-3)
10Â kW 500 V AC 50/60 Hz AC-3)
10Â kW 660…690 V AC 50/60 Hz AC-3)
4Â kW 400 V AC 50/60 Hz AC-4)
|
|
motor power HP (UL / CSA)
|
1Â hp 115 V AC 50/60 Hz 1 phase
3Â hp 230/240 V AC 50/60 Hz 1 phase
5Â hp 200/208 V AC 50/60 Hz 3 phases
5Â hp 230/240 V AC 50/60 Hz 3 phases
10Â hp 460/480 V AC 50/60 Hz 3 phases
15Â hp 575/600 V AC 50/60 Hz 3 phases
|
|
control circuit type
|
AC 50/60 Hz
|
|
[Uc] control circuit voltage
|
220 V AC 50/60 Hz
|
|
auxiliary contact composition
|
1 NO + 1 NC
|
|
[Uimp] rated impulse withstand voltage
|
6Â kV IEC 60947
|
|
overvoltage category
|
III
|
|
[Ith] conventional free air thermal current
|
10 A 140 °F (60 °C) signalling circuit
32 A 140 °F (60 °C) power circuit
|
|
Irms rated making capacity
|
140Â A AC signalling circuit IEC 60947-5-1
250Â A DC signalling circuit IEC 60947-5-1
300Â A 440 V power circuit IEC 60947
|
|
rated breaking capacity
|
300Â A 440 V power circuit IEC 60947
|
|
[Icw] rated short-time withstand current
|
145 A 104 °F (40 °C) – 10 s power circuit
240 A 104 °F (40 °C) – 1 s power circuit
40 A 104 °F (40 °C) – 10 min power circuit
84 A 104 °F (40 °C) – 1 min power circuit
100Â A – 1 s signalling circuit
120Â A – 500 ms signalling circuit
140Â A – 100 ms signalling circuit
|
|
associated fuse rating
|
10Â A gG signalling circuit IEC 60947-5-1
50Â A gG <= 690 V type 1 power circuit
35Â A gG <= 690 V type 2 power circuit
|
|
average impedance
|
2.5Â mOhm – Ith 32Â A 50 Hz power circuit
|
|
[Ui] rated insulation voltage
|
Power circuit 690Â V IEC 60947-4-1
Power circuit 600Â V CSA
Power circuit 600Â V UL
Signalling circuit 690Â V IEC 60947-1
Signalling circuit 600Â V CSA
Signalling circuit 600Â V UL
|
|
electrical durability
|
1.65Â Mcycles 18Â A AC-3 <= 440 V
1Â Mcycles 32Â A AC-1 <= 440 V
|
|
power dissipation per pole
|
2.5Â W AC-1
0.8Â W AC-3
|
|
safety cover
|
With
|
|
mounting support
|
Plate
Rail
|
|
standards
|
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
|
|
product certifications
|
GOST
UL
RINA
CCC
DNV
BV
GL
CSA
LROS (Lloyds register of shipping)
|
|
connections – terminals
|
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end
Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible with cable end
Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)solid without cable end
Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)solid without cable end
Power circuit screw clamp terminals 1 0.00…0.01 in² (1.5…6 mm²)flexible without cable end
Power circuit screw clamp terminals 2 0.00…0.01 in² (1.5…6 mm²)flexible without cable end
Power circuit screw clamp terminals 1 0.00…0.01 in² (1…6 mm²)flexible with cable end
Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible with cable end
Power circuit screw clamp terminals 1 0.00…0.01 in² (1.5…6 mm²)solid without cable end
Power circuit screw clamp terminals 2 0.00…0.01 in² (1.5…6 mm²)solid without cable end
|
|
tightening torque
|
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Power circuit 15.05Â lbf.in (1.7Â N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05Â lbf.in (1.7Â N.m) screw clamp terminals Philips No 2
|
|
operating time
|
12…22 ms closing
4…19 ms opening
|
|
safety reliability level
|
B10d = 1369863Â cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000Â cycles contactor with mechanical load EN/ISO 13849-1
|
|
mechanical durability
|
15Â Mcycles
|
|
maximum operating rate
|
3600 cyc/h 140 °F (60 °C)
|
|
Reviews
There are no reviews yet.