Description
ÖLFLEX CLASSIC 110 4G16
- VDE-registered oil-resistant PVC control cable for a wide range of applications
- CPR: Article number choice under www.lappkabel.com/cpr
- VDE certificate of conformity with factory surveillance
PRODUCT DETAILS
Benefits
- Wide choice of standardized lengths and individual cuts
- Very broad range, items with up to 100 conductors
Application range
- For fixed installation as well as occasional flexing at free, non-continuously recurring movement without tensile load
- Dry or damp rooms that are subject to medium mechanical loads
- Suitable for torsional applications which are typical for the loop in wind turbine generators (WTG)
- In power chains for a travelling distance up to 5 m and 0,2 … 1 million bending cycles, for following dimensions: 0,5 to 2.5mm² and 2 to 7 conductors
Product features
- Flame-retardant according IEC 60332-1-2
- Good chemical resistance, see catalogue appendix T1
- Oil-resistant according to DIN EN 50290-2-22 (TM54)
Norm References / Approvals
- VDE reg. no. 7030 for the following sizes:up to 2.5 mm²: 2 – 65 coresfrom 4 mm²: 2 – 7 coresfrom 25 mm²: 2 – 5 cores
Product Make-up
- Fine-wire strand made of bare copper wires
- PVC insulation LAPP P8/1
- Cores twisted in layers
- PVC outer sheath, grey (similar RAL 7001)
TECHNICAL DATA
- Download DATASHEET (PDF)
- Minimum Bending Radius
- Occasional flexing: 10 x outer diameterIn power chains: 15 x outer diameter
- Fixed installation: 4 x outer diameter
- Temperature Range
- Occasional flexing: -15°C to +70°C In power chains: -5°C to +70°C
- Fixed installation: -40°C to +80°C
- Core Identification Code
- Black with white numbers acc. to VDE 0293-1
- Protective Conductor
- G = with GN-YE protective conductor
- X = without protective conductor
- Nominal Voltage
- U0/U: 300/500 V
- Test Voltage
- 4000 V
- Conductor Stranding
- Fine wire according to DIN EN 60228 (VDE 0295), class 5 / IEC 60228 class 5
- Classification ETIM 5
- ETIM 5.0 Class-ID: EC000104
- ETIM 5.0 Class-Description: Control cable
- Torsion movement in WTG
- TW-0 & TW-1, refer to Appendix T0
Reviews
There are no reviews yet.