Main
|
range
|
TeSys
|
product name
|
TeSys D
|
product or component type
|
Contactor
|
device short name
|
LC1D
|
contactor application
|
Resistive load
|
Motor control
|
utilisation category
|
AC-3
|
AC-4
|
AC-1
|
poles description
|
3P
|
power pole contact composition
|
3 NO
|
[Ue] rated operational voltage
|
Power circuit: <= 690 V AC 25…400 Hz
|
Power circuit: <= 300 V DC
|
[Ie] rated operational current
|
25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
|
12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
|
motor power kW
|
3 kW at 220…230 V AC 50/60 Hz (AC-3)
|
5.5 kW at 380…400 V AC 50/60 Hz (AC-3)
|
5.5 kW at 415…440 V AC 50/60 Hz (AC-3)
|
7.5 kW at 500 V AC 50/60 Hz (AC-3)
|
7.5 kW at 660…690 V AC 50/60 Hz (AC-3)
|
3.7 kW at 400 V AC 50/60 Hz (AC-4)
|
motor power HP (UL / CSA)
|
0.5 hp at 115 V AC 50/60 Hz for 1 phase motors
|
2 hp at 230/240 V AC 50/60 Hz for 1 phase motors
|
3 hp at 200/208 V AC 50/60 Hz for 3 phases motors
|
3 hp at 230/240 V AC 50/60 Hz for 3 phases motors
|
7.5 hp at 460/480 V AC 50/60 Hz for 3 phases motors
|
10 hp at 575/600 V AC 50/60 Hz for 3 phases motors
|
control circuit type
|
AC at 50/60 Hz
|
[Uc] control circuit voltage
|
110 V AC 50/60 Hz
|
auxiliary contact composition
|
1 NO + 1 NC
|
[Uimp] rated impulse withstand voltage
|
6 kV conforming to IEC 60947
|
overvoltage category
|
III
|
[Ith] conventional free air thermal current
|
25 A (at 60 °C) for power circuit
|
10 A (at 60 °C) for signalling circuit
|
Irms rated making capacity
|
250 A at 440 V for power circuit conforming to IEC 60947
|
140 A AC for signalling circuit conforming to IEC 60947-5-1
|
250 A DC for signalling circuit conforming to IEC 60947-5-1
|
rated breaking capacity
|
250 A at 440 V for power circuit conforming to IEC 60947
|
[Icw] rated short-time withstand current
|
105 A 40 °C – 10 s for power circuit
|
210 A 40 °C – 1 s for power circuit
|
30 A 40 °C – 10 min for power circuit
|
61 A 40 °C – 1 min for power circuit
|
100 A – 1 s for signalling circuit
|
120 A – 500 ms for signalling circuit
|
140 A – 100 ms for signalling circuit
|
associated fuse rating
|
10 A gG for signalling circuit conforming to IEC 60947-5-1
|
40 A gG at <= 690 V coordination type 1 for power circuit
|
25 A gG at <= 690 V coordination type 2 for power circuit
|
average impedance
|
2.5 mOhm – Ith 25 A 50 Hz for power circuit
|
[Ui] rated insulation voltage
|
Power circuit: 690 V conforming to IEC 60947-4-1
|
Power circuit: 600 V CSA certified
|
Power circuit: 600 V UL certified
|
Signalling circuit: 690 V conforming to IEC 60947-1
|
Signalling circuit: 600 V CSA certified
|
Signalling circuit: 600 V UL certified
|
electrical durability
|
2 Mcycles 12 A AC-3 at Ue <= 440 V
|
0.8 Mcycles 25 A AC-1 at Ue <= 440 V
|
power dissipation per pole
|
0.36 W AC-3
|
1.56 W AC-1
|
Front cover
|
With
|
mounting support
|
Rail
|
Plate
|
standards
|
CSA C22.2 No 14
|
EN 60947-4-1
|
EN 60947-5-1
|
IEC 60947-4-1
|
IEC 60947-5-1
|
UL 508
|
product certifications
|
CCC
|
BV
|
CSA
|
GL
|
UL
|
RINA
|
GOST
|
LROS (Lloyds register of shipping)
|
DNV
|
connections – terminals
|
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
|
Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
|
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
|
Power circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
|
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
|
Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
|
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
|
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
|
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
|
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
|
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
|
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
|
tightening torque
|
Power circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
|
Power circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2
|
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
|
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2
|
operating time
|
12…22 ms closing
|
4…19 ms opening
|
safety reliability level
|
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
|
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
|
mechanical durability
|
15 Mcycles
|
maximum operating rate
|
3600 cyc/h 60 °C
|
Complementary
|
coil technology
|
Without built-in suppressor module
|
inrush power in VA
|
70 VA 60 Hz cos phi 0.75 (at 20 °C)
|
70 VA 50 Hz cos phi 0.75 (at 20 °C)
|
hold-in power consumption in VA
|
7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
|
7 VA 50 Hz cos phi 0.3 (at 20 °C)
|
heat dissipation
|
2…3 W at 50/60 Hz
|
auxiliary contacts type
|
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
|
type mirror contact 1 NC conforming to IEC 60947-4-1
|
signalling circuit frequency
|
25…400 Hz
|
minimum switching current
|
5 mA for signalling circuit
|
minimum switching voltage
|
17 V for signalling circuit
|
non-overlap time
|
1.5 ms on de-energisation between NC and NO contact
|
1.5 ms on energisation between NC and NO contact
|
insulation resistance
|
> 10 MOhm for signalling circuit
|
contact compatibility
|
M2
|
compatibility code
|
LC1D
|
motor power range
|
4…6 kW at 380…440 V 3 phases
|
4…6 kW at 480…500 V 3 phases
|
2.2…3 kW at 200…240 V 3 phases
|
motor starter type
|
Direct on-line contactor
|
contactor coil voltage
|
110 V AC standard
|
Environment
|
IP degree of protection
|
IP20 front face conforming to IEC 60529
|
protective treatment
|
TH conforming to IEC 60068-2-30
|
pollution degree
|
3
|
ambient air temperature for storage
|
-60…80 °C
|
operating altitude
|
3000 m without derating
|
fire resistance
|
850 °C conforming to IEC 60695-2-1
|
flame retardance
|
V1 conforming to UL 94
|
mechanical robustness
|
Vibrations contactor open: 2 Gn, 5…300 Hz
|
Vibrations contactor closed: 4 Gn, 5…300 Hz
|
Shocks contactor open: 10 Gn for 11 ms
|
Shocks contactor closed: 15 Gn for 11 ms
|
height
|
77 mm
|
width
|
45 mm
|
depth
|
86 mm
|
net weight
|
0.325 kg
|
Packing Units
|
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Weight
|
356 g
|
Package 1 Height
|
5 cm
|
Package 1 width
|
9.2 cm
|
Package 1 Length
|
11.2 cm
|
Unit Type of Package 2
|
S02
|
Number of Units in Package 2
|
20
|
Package 2 Weight
|
7.411 kg
|
Package 2 Height
|
15 cm
|
Package 2 width
|
30 cm
|
Package 2 Length
|
40 cm
|
Unit Type of Package 3
|
P06
|
Number of Units in Package 3
|
320
|
Package 3 Weight
|
129.38 kg
|
Package 3 Height
|
80 cm
|
Package 3 width
|
80 cm
|
Package 3 Length
|
60 cm
|
Offer Sustainability
|
Sustainable offer status
|
Green Premium product
|
REACh free of SVHC
|
Yes
|
EU RoHS Directive
|
Compliant
|
|
Toxic heavy metal free
|
Yes
|
Mercury free
|
Yes
|
RoHS exemption information
|
|
China RoHS Regulation
|
|
Pro-active China RoHS declaration (out of China RoHS legal scope)
|
Environmental Disclosure
|
|
Circularity Profile
|
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
PVC free
|
Yes
|
Contractual warranty
|
Warranty
|
18 months
|
Reviews
There are no reviews yet.