Main |
range | TeSys |
product name | TeSys D |
product or component type | Contactor |
device short name | LC1D |
contactor application | Resistive load |
Motor control |
utilisation category | AC-3 |
AC-4 |
AC-1 |
poles description | 3P |
power pole contact composition | 3 NO |
[Ue] rated operational voltage | Power circuit: <= 690 V AC 25…400 Hz |
Power circuit: <= 300 V DC |
[Ie] rated operational current | 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit |
12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit |
motor power kW | 3 kW at 220…230 V AC 50/60 Hz (AC-3) |
5.5 kW at 380…400 V AC 50/60 Hz (AC-3) |
5.5 kW at 415…440 V AC 50/60 Hz (AC-3) |
7.5 kW at 500 V AC 50/60 Hz (AC-3) |
7.5 kW at 660…690 V AC 50/60 Hz (AC-3) |
3.7 kW at 400 V AC 50/60 Hz (AC-4) |
motor power HP (UL / CSA) | 0.5 hp at 115 V AC 50/60 Hz for 1 phase motors |
2 hp at 230/240 V AC 50/60 Hz for 1 phase motors |
3 hp at 200/208 V AC 50/60 Hz for 3 phases motors |
3 hp at 230/240 V AC 50/60 Hz for 3 phases motors |
7.5 hp at 460/480 V AC 50/60 Hz for 3 phases motors |
10 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
control circuit type | AC at 50/60 Hz |
[Uc] control circuit voltage | 110 V AC 50/60 Hz |
auxiliary contact composition | 1 NO + 1 NC |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
overvoltage category | III |
[Ith] conventional free air thermal current | 25 A (at 60 °C) for power circuit |
10 A (at 60 °C) for signalling circuit |
Irms rated making capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
140 A AC for signalling circuit conforming to IEC 60947-5-1 |
250 A DC for signalling circuit conforming to IEC 60947-5-1 |
rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current | 105 A 40 °C – 10 s for power circuit |
210 A 40 °C – 1 s for power circuit |
30 A 40 °C – 10 min for power circuit |
61 A 40 °C – 1 min for power circuit |
100 A – 1 s for signalling circuit |
120 A – 500 ms for signalling circuit |
140 A – 100 ms for signalling circuit |
associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1 |
40 A gG at <= 690 V coordination type 1 for power circuit |
25 A gG at <= 690 V coordination type 2 for power circuit |
average impedance | 2.5 mOhm – Ith 25 A 50 Hz for power circuit |
[Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1 |
Power circuit: 600 V CSA certified |
Power circuit: 600 V UL certified |
Signalling circuit: 690 V conforming to IEC 60947-1 |
Signalling circuit: 600 V CSA certified |
Signalling circuit: 600 V UL certified |
electrical durability | 2 Mcycles 12 A AC-3 at Ue <= 440 V |
0.8 Mcycles 25 A AC-1 at Ue <= 440 V |
power dissipation per pole | 0.36 W AC-3 |
1.56 W AC-1 |
Front cover | With |
mounting support | Rail |
Plate |
standards | CSA C22.2 No 14 |
EN 60947-4-1 |
EN 60947-5-1 |
IEC 60947-4-1 |
IEC 60947-5-1 |
UL 508 |
product certifications | CCC |
BV |
CSA |
GL |
UL |
RINA |
GOST |
LROS (Lloyds register of shipping) |
DNV |
connections – terminals | Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end |
Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end |
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end |
Power circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end |
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end |
Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end |
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end |
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end |
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end |
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end |
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end |
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end |
tightening torque | Power circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm |
Power circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2 |
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm |
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2 |
operating time | 12…22 ms closing |
4…19 ms opening |
safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 |
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
mechanical durability | 15 Mcycles |
maximum operating rate | 3600 cyc/h 60 °C |
Complementary |
coil technology | Without built-in suppressor module |
inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C) |
70 VA 50 Hz cos phi 0.75 (at 20 °C) |
hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C) |
7 VA 50 Hz cos phi 0.3 (at 20 °C) |
heat dissipation | 2…3 W at 50/60 Hz |
auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 |
type mirror contact 1 NC conforming to IEC 60947-4-1 |
signalling circuit frequency | 25…400 Hz |
minimum switching current | 5 mA for signalling circuit |
minimum switching voltage | 17 V for signalling circuit |
non-overlap time | 1.5 ms on de-energisation between NC and NO contact |
1.5 ms on energisation between NC and NO contact |
insulation resistance | > 10 MOhm for signalling circuit |
contact compatibility | M2 |
compatibility code | LC1D |
motor power range | 4…6 kW at 380…440 V 3 phases |
4…6 kW at 480…500 V 3 phases |
2.2…3 kW at 200…240 V 3 phases |
motor starter type | Direct on-line contactor |
contactor coil voltage | 110 V AC standard |
Environment |
IP degree of protection | IP20 front face conforming to IEC 60529 |
protective treatment | TH conforming to IEC 60068-2-30 |
pollution degree | 3 |
ambient air temperature for storage | -60…80 °C |
operating altitude | 3000 m without derating |
fire resistance | 850 °C conforming to IEC 60695-2-1 |
flame retardance | V1 conforming to UL 94 |
mechanical robustness | Vibrations contactor open: 2 Gn, 5…300 Hz |
Vibrations contactor closed: 4 Gn, 5…300 Hz |
Shocks contactor open: 10 Gn for 11 ms |
Shocks contactor closed: 15 Gn for 11 ms |
height | 77 mm |
width | 45 mm |
depth | 86 mm |
net weight | 0.325 kg |
Packing Units |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Weight | 356 g |
Package 1 Height | 5 cm |
Package 1 width | 9.2 cm |
Package 1 Length | 11.2 cm |
Unit Type of Package 2 | S02 |
Number of Units in Package 2 | 20 |
Package 2 Weight | 7.411 kg |
Package 2 Height | 15 cm |
Package 2 width | 30 cm |
Package 2 Length | 40 cm |
Unit Type of Package 3 | P06 |
Number of Units in Package 3 | 320 |
Package 3 Weight | 129.38 kg |
Package 3 Height | 80 cm |
Package 3 width | 80 cm |
Package 3 Length | 60 cm |
Offer Sustainability |
Sustainable offer status | Green Premium product |
REACh free of SVHC | Yes |
EU RoHS Directive | Compliant |
|
Toxic heavy metal free | Yes |
Mercury free | Yes |
RoHS exemption information | |
China RoHS Regulation | |
Pro-active China RoHS declaration (out of China RoHS legal scope) |
Environmental Disclosure | |
Circularity Profile | |
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins |
PVC free | Yes |
Contractual warranty |
Warranty | 18 months |
Reviews
There are no reviews yet.