TeSys D contactor – 3P 3 NO – AC-3 – <= 440 V 38 A - 220 V AC 50/60 Hz coil LC1D38M7

TeSys D contactor – 3P 3 NO – AC-3 – <= 440 V 38 A - 220 V AC 50/60 Hz coil LC1D38M7

SKU: LC1D38M7 Category: Tag:

Compare

Description

Main

range

TeSys

product name

TeSys D

product or component type

Contactor

device short name

LC1D

contactor application

Motor control
Resistive load

utilisation category

AC-3
AC-4
AC-1

poles description

3P

power pole contact composition

3 NO

[Ue] rated operational voltage

Power circuit: <= 690 V AC 25…400 Hz
Power circuit: <= 300 V DC

[Ie] rated operational current

50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
38 A (at <60 °C) at <= 440 V AC AC-3 for power circuit

motor power kW

18.5 kW at 500 V AC 50/60 Hz (AC-3)
18.5 kW at 660…690 V AC 50/60 Hz (AC-3)
7.5 kW at 400 V AC 50/60 Hz (AC-4)
18.5 kW at 380…400 V AC 50/60 Hz (AC-3)
9 kW at 220…230 V AC 50/60 Hz (AC-3)
18.5 kW at 415…440 V AC 50/60 Hz (AC-3)

motor power HP (UL / CSA)

10 hp at 230/240 V AC 50/60 Hz for 3 phases motors
10 hp at 200/208 V AC 50/60 Hz for 3 phases motors
5 hp at 240 V AC 50/60 Hz for 1 phase motors
20 hp at 480 V AC 50/60 Hz for 3 phases motors
25 hp at 600 V AC 50/60 Hz for 3 phases motors

control circuit type

AC at 50/60 Hz

[Uc] control circuit voltage

220 V AC 50/60 Hz

auxiliary contact composition

1 NO + 1 NC

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

overvoltage category

III

[Ith] conventional free air thermal current

10 A (at 60 °C) for signalling circuit
50 A (at 60 °C) for power circuit

Irms rated making capacity

140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
550 A at 440 V for power circuit conforming to IEC 60947

rated breaking capacity

550 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current

60 A 40 °C – 10 min for power circuit
430 A 40 °C – 1 s for power circuit
150 A 40 °C – 1 min for power circuit
310 A 40 °C – 10 s for power circuit
100 A – 1 s for signalling circuit
120 A – 500 ms for signalling circuit
140 A – 100 ms for signalling circuit

associated fuse rating

10 A gG for signalling circuit conforming to IEC 60947-5-1
63 A gG at <= 690 V coordination type 1 for power circuit
63 A gG at <= 690 V coordination type 2 for power circuit

average impedance

2 mOhm – Ith 50 A 50 Hz for power circuit

[Ui] rated insulation voltage

Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1

electrical durability

1.4 Mcycles 50 A AC-1 at Ue <= 440 V
1.4 Mcycles 38 A AC-3 at Ue <= 440 V

power dissipation per pole

5 W AC-1
3 W AC-3

safety cover

With

mounting support

Rail
Plate

standards

CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508

product certifications

LROS (Lloyds register of shipping)
BV
GL
DNV
RINA
CCC
GOST
UL
CSA

connections – terminals

Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm²flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…10 mm²flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm²flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm²solid without cable end
Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²solid without cable end

tightening torque

Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2
Power circuit: 2.5 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Power circuit: 2.5 N.m – on screw clamp terminals – with screwdriver Philips No 2

operating time

4…19 ms opening
12…22 ms closing

safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

mechanical durability

15 Mcycles

maximum operating rate

3600 cyc/h 60 °C

Complementary

coil technology

Without built-in suppressor module

control circuit voltage limits

Drop-out: 0.3…0.6 Uc AC 50/60 Hz (at 60 °C)
Operational: 0.8…1.1 Uc AC 50 Hz (at 60 °C)
Operational: 0.85…1.1 Uc AC 60 Hz (at 60 °C)

inrush power in VA

70 VA 60 Hz cos phi 0.75 (at 20 °C)
70 VA 50 Hz cos phi 0.75 (at 20 °C)

hold-in power consumption in VA

7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
7 VA 50 Hz cos phi 0.3 (at 20 °C)

heat dissipation

2…3 W at 50/60 Hz

auxiliary contacts type

type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1

signalling circuit frequency

25…400 Hz

minimum switching current

5 mA for signalling circuit

minimum switching voltage

17 V for signalling circuit

non-overlap time

1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact

insulation resistance

> 10 MOhm for signalling circuit

Environment

IP degree of protection

IP20 front face conforming to IEC 60529

protective treatment

TH conforming to IEC 60068-2-30

pollution degree

3

ambient air temperature for operation

-5…60 °C

ambient air temperature for storage

-60…80 °C

permissible ambient air temperature around the device

-40…70 °C at Uc

operating altitude

3000 m without

fire resistance

850 °C conforming to IEC 60695-2-1

flame retardance

V1 conforming to UL 94

mechanical robustness

Vibrations contactor open: 2 Gn, 5…300 Hz
Vibrations contactor closed: 4 Gn, 5…300 Hz
Shocks contactor closed: 15 Gn for 11 ms
Shocks contactor open: 8 Gn for 11 ms

height

85 mm

width

45 mm

depth

92 mm

net weight

0.38 kg

Offer Sustainability

Sustainable offer status

Green Premium product

REACh Regulation

REACh Declaration

EU RoHS Directive

Compliant
EU RoHS Declaration

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

China RoHS declaration

Environmental Disclosure

Product Environmental Profile

Circularity Profile

End of Life Information

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Contractual warranty

Warranty

18 months

Reviews

There are no reviews yet.

Be the first to review “TeSys D contactor – 3P 3 NO – AC-3 – <= 440 V 38 A - 220 V AC 50/60 Hz coil LC1D38M7”

Your email address will not be published. Required fields are marked *