range
|
TeSys
|
|
product name
|
TeSys D
|
|
product or component type
|
Contactor
|
|
device short name
|
LC1D
|
|
contactor application
|
Resistive load
Motor control
|
|
utilisation category
|
AC-1
AC-4
AC-3
|
|
poles description
|
3P
|
|
power pole contact composition
|
3 NO
|
|
[Ue] rated operational voltage
|
Power circuit: <= 690 V AC 25…400 Hz
Power circuit: <= 300 V DC
|
|
[Ie] rated operational current
|
50 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
|
|
motor power kW
|
15 kW at 220…230 V AC 50/60 Hz (AC-3)
22 kW at 380…400 V AC 50/60 Hz (AC-3)
30 kW at 500 V AC 50/60 Hz (AC-3)
33 kW at 660…690 V AC 50/60 Hz (AC-3)
25 kW at 415 V AC 50/60 Hz (AC-3)
30 kW at 440 V AC 50/60 Hz (AC-3)
11 kW at 400 V AC 50/60 Hz (AC-4)
|
|
motor power HP (UL / CSA)
|
3 hp at 115 V AC 50/60 Hz for 1 phase motors
7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
15 hp at 200/208 V AC 50/60 Hz for 3 phases motors
15 hp at 230/240 V AC 50/60 Hz for 3 phases motors
40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
40 hp at 575/600 V AC 50/60 Hz for 3 phases motors
|
|
control circuit type
|
AC at 50/60 Hz
|
|
[Uc] control circuit voltage
|
24 V AC 50/60 Hz
|
|
auxiliary contact composition
|
1 NO + 1 NC
|
|
[Uimp] rated impulse withstand voltage
|
6 kV conforming to IEC 60947
|
|
overvoltage category
|
III
|
|
[Ith] conventional free air thermal current
|
10 A (at 60 °C) for signalling circuit
80 A (at 60 °C) for power circuit
|
|
Irms rated making capacity
|
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
900 A at 440 V for power circuit conforming to IEC 60947
|
|
rated breaking capacity
|
900 A at 440 V for power circuit conforming to IEC 60947
|
|
[Icw] rated short-time withstand current
|
400 A 40 °C – 10 s for power circuit
810 A 40 °C – 1 s for power circuit
84 A 40 °C – 10 min for power circuit
208 A 40 °C – 1 min for power circuit
100 A – 1 s for signalling circuit
120 A – 500 ms for signalling circuit
140 A – 100 ms for signalling circuit
|
|
associated fuse rating
|
10 A gG for signalling circuit conforming to IEC 60947-5-1
100 A gG at <= 690 V coordination type 1 for power circuit
100 A gG at <= 690 V coordination type 2 for power circuit
|
|
average impedance
|
1.5 mOhm – Ith 80 A 50 Hz for power circuit
|
|
[Ui] rated insulation voltage
|
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1
|
|
electrical durability
|
1.45 Mcycles 50 A AC-3 at Ue <= 440 V
1.1 Mcycles 80 A AC-1 at Ue <= 440 V
|
|
power dissipation per pole
|
3.7 W AC-3
9.6 W AC-1
|
|
safety cover
|
With
|
|
mounting support
|
Plate
Rail
|
|
standards
|
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
|
|
product certifications
|
DNV
LROS (Lloyds register of shipping)
CCC
GOST
BV
RINA
CSA
UL
GL
|
|
connections – terminals
|
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: screw connection 1 cable(s) 1…35 mm²flexible without cable end
Power circuit: screw connection 2 cable(s) 1…25 mm²flexible without cable end
Power circuit: screw connection 1 cable(s) 1…35 mm²flexible with cable end
Power circuit: screw connection 2 cable(s) 1…25 mm²flexible with cable end
Power circuit: screw connection 1 cable(s) 1…35 mm²solid without cable end
Power circuit: screw connection 2 cable(s) 1…25 mm²solid without cable end
|
|
tightening torque
|
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2
Power circuit: 8 N.m – on EverLink BTR screw connectors – cable 25…35 mm² hexagonal screw head 4 mm
Power circuit: 5 N.m – on EverLink BTR screw connectors – cable 1…25 mm² hexagonal screw head 4 mm
|
|
operating time
|
4…19 ms opening
12…26 ms closing
|
|
safety reliability level
|
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
|
|
mechanical durability
|
6 Mcycles
|
|
maximum operating rate
|
3600 cyc/h 60 °C
|
|
Reviews