range | TeSys | |
---|
product name | TeSys D | |
---|
product or component type | Contactor | |
---|
device short name | LC1D | |
---|
contactor application | Motor control
Resistive load | |
---|
utilisation category | AC-3
AC-4
AC-1 | |
---|
poles description | 3P | |
---|
power pole contact composition | 3 NO | |
---|
[Ue] rated operational voltage | Power circuit: <= 690 V AC 25…400 Hz
Power circuit: <= 300 V DC | |
---|
[Ie] rated operational current | 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit | |
---|
motor power kW | 11 kW at 400 V AC 50/60 Hz (AC-4)
18.5 kW at 220…230 V AC 50/60 Hz (AC-3)
30 kW at 380…400 V AC 50/60 Hz (AC-3)
37 kW at 500 V AC 50/60 Hz (AC-3)
37 kW at 660…690 V AC 50/60 Hz (AC-3) | |
---|
motor power HP (UL / CSA) | 40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
5 hp at 115 V AC 50/60 Hz for 1 phase motors
10 hp at 230/240 V AC 50/60 Hz for 1 phase motors
20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
20 hp at 230/240 V AC 50/60 Hz for 3 phases motors
50 hp at 575/600 V AC 50/60 Hz for 3 phases motors | |
---|
control circuit type | AC at 50/60 Hz | |
---|
[Uc] control circuit voltage | 220 V AC 50/60 Hz | |
---|
auxiliary contact composition | 1 NO + 1 NC | |
---|
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 | |
---|
overvoltage category | III | |
---|
[Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit
80 A (at 60 °C) for power circuit | |
---|
Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1000 A at 440 V for power circuit conforming to IEC 60947 | |
---|
rated breaking capacity | 1000 A at 440 V for power circuit conforming to IEC 60947 | |
---|
[Icw] rated short-time withstand current | 520 A 40 °C – 10 s for power circuit
900 A 40 °C – 1 s for power circuit
110 A 40 °C – 10 min for power circuit
260 A 40 °C – 1 min for power circuit
100 A – 1 s for signalling circuit
120 A – 500 ms for signalling circuit
140 A – 100 ms for signalling circuit | |
---|
associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1
125 A gG at <= 690 V coordination type 1 for power circuit
125 A gG at <= 690 V coordination type 2 for power circuit | |
---|
average impedance | 1.5 mOhm – Ith 80 A 50 Hz for power circuit | |
---|
[Ui] rated insulation voltage | Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1 | |
---|
electrical durability | 1.4 Mcycles 80 A AC-1 at Ue <= 440 V
1.45 Mcycles 65 A AC-3 at Ue <= 440 V | |
---|
power dissipation per pole | 9.6 W AC-1
6.3 W AC-3 | |
---|
safety cover | With | |
---|
mounting support | Rail
Plate | |
---|
standards | CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508 | |
---|
product certifications | UL
CCC
GOST
CSA | |
---|
connections – terminals | Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: EverLink BTR screw connectors 1 cable(s) 1…35 mm²flexible without cable end
Power circuit: EverLink BTR screw connectors 2 cable(s) 1…25 mm²flexible without cable end
Power circuit: EverLink BTR screw connectors 1 cable(s) 1…35 mm²flexible with cable end
Power circuit: EverLink BTR screw connectors 2 cable(s) 1…25 mm²flexible with cable end
Power circuit: EverLink BTR screw connectors 1 cable(s) 1…35 mm²solid without cable end
Power circuit: EverLink BTR screw connectors 2 cable(s) 1…25 mm²solid without cable end | |
---|
tightening torque | Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2
Power circuit: 8 N.m – on EverLink BTR screw connectors – cable 25…35 mm² hexagonal screw head 4 mm
Power circuit: 5 N.m – on EverLink BTR screw connectors – cable 1…25 mm² hexagonal screw head 4 mm | |
---|
operating time | 4…19 ms opening
12…26 ms closing | |
---|
safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 | |
---|
mechanical durability | 6 Mcycles | |
---|
maximum operating rate | 3600 cyc/h 60 °C | |
---|